Smart Evo 1
The most complete control panel for sewage and pumping systems ever!
SMART EVO 1 is the best-seller control panel from Elentek, suitable to multiple applications both for clean water systems (emptying, filling, pressurization) and dirty water (emptying and draining waste water).
Compact, economical and easy to install and use.
General technical features
-
Power supply 1phase 100-240Vac 50/60Hz (SMART EVO-Mono);
-
Power supply 3phase 310-450Vac 50/60Hz (SMART EVO-Tri);
NO input G/P1; -
T1 input for motor clicson;
-
Input for 3 single-pole probes (COM-MIN-MAX);
-
Input G.A. normally open for alarm activation;
-
Push-buttons for selecting operation AUTOMATIC-0-MANUAL(temporary);
-
DIP-SWITCH selectors for:
-
enabling level alarm from probes;
-
thermal cut-out activation delay 5/10 seconds;
-
alarm output settings;
-
alarm reset enable from motor clicson;
-
filling/emptying mode;
-
enabling start/stop float function;
-
delay of electronic board activation on power mains return;
-
-
Autotest anti-seize (2 sec. every 48 hours);
-
Green led: power ON / failure or incorrect phase sequence;
-
Green led: automatic mode enabled;
-
Green led: motor active;
-
Red led: level alarm from sensors or GA input;
-
Red led: motor overload alarm/minimum current alarm;
-
Red led: motor clicson activation alarm;
-
Electronic control of maximum current due to overload, with assisted calibration;
-
Electronic control of minimum current due to dry run, with assisted calibration;
-
Automatic reset due to minimum current alarm;
-
Protection of auxiliary circuits and motor with fuses;
-
Cumulative alarm output with voltage-free contacts (NC-C-NO resistive load - 5A / 250V);
-
Cumulative alarm output, live (12Vcc / 100mA);
-
Door lock isolator switch;
-
Provision for start-up capacitors, single phase version (not included);
-
Box in ABS, IP55;
-
Ambient temperature: -5/+40 °C;
-
Relative humidity 50% at 40 °C (condensate free).
Highlights
Electronic board
SMART EVO 1 electronic board is equipped with a dip-switch module with 7 selectors to set the following operation modes: signaling of level alarm from probe input, delay of intervention of amperometric protection, setting of alarm outputs, reset mode of alarm from motor clicson, filling / emptying operating mode, start/stop function, board activation delay in case of mains return.
The amperometric protection for overcurrent and minimum current (dry running protection) is adjustable using the trimmers on the board.
App
The peculiarity of the electronic board of SMART EVO control panel is a dedicated App available for free both in Google Play and in the App Store and usable with the optional Bluetooth Express card to be installed quickly and easily on the motherboard of SMART EVO.
The app allows you to control and manage the operation of the electrical panel directly from your smartphone or tablet adding functions such as hour run counter, starting counter, amp meter, history of the 20 most recent alarms, status of inputs and outputs and the possibility to set dip-switches and trimmers from the smartphone increasing the precision of the set-up value.
Components
The motor protection fuses are supplied as a standard with SMART EVO 1 and can be replaced by circuit breaker on request.
An isolator switch cuts the main power supply input to cut-off voltage to the panel and guarantees max safety when opening the control panel.
The motors and the external controls (floats, pressure switches,…) can be connected to the terminal inside the panel.
Functions indications
SMART EVO 1 control panel is equipped with led lights on the frontpanel to indicate: mains supply, pump running, automatic operation, phase failure/sequence, minimum current alarm, level alarm from probes or float switches, overtemperature motor alarm.
Anti seizing function
The control panel SMART EVO can be set with a pumps auto-test active when the panel is in automatic mode operation.
The auto-test has a fix non-adjustable time and will activate the pump to run for 2 seconds every 48 hours.
Alarms
The SMART EVO 1 electronic board has an alarm output with volt free contacts and an energized output 12Vcc – 100mA where to connect an acoustic or visual alarm which activates for all the alarm status of which the system is equipped: minimum current alarm (dry running), overcurrent alarm, phase failure/sequence (three-phase model only), level alarm from probes or float/pressure switch input, overtemperature alarm.
Applications
_edited.jpg)
Filling
with float switch and min current
SMART EVO 1 application for filling with float switch and dry running protection by mininimum current control.
_edited.jpg)
Pressurization/ Irrigation
with pressure switch and probes
SMART EVO 1 application for pressurization or irrigation with pressure switch and dry running protection by level probes.
_edited.jpg)
Pressurization/ Irrigation
with pressure switch and min current
pressurization or irrigation with pressure switch and dry running protection by minimum current control.
_edited_jp.jpg)
Emptying/ Drainage
sewage water
SMART EVO 1 application for emptying/drainage sewage water with float switches.
_edited_jp.jpg)
Filling
with level probes and float switches
SMART EVO 1 application for filling a tank with max level float switch and dry running protection by level probes.
_edited_jp.jpg)
Pressurization/ Irrigation
with pressure switch and float switch
SMART EVO 1 application for pressurization or irrigation with start pressure switch and dry running protection by float switch.
Models
Accessories
App
With the SMART EVO APP you can control the status of the electric panel and of the inputs and to carry on operations without having to open the panel.
You can download the SMART EVO APP for free both from GOOGLE PLAY and APP STORE.
.jpg)
Language
Language set-up.
.jpg)
Pair device
Search for the SMART EVO control panel to be connected via bluetooth.
.jpg)
Password
Enter password according to the type of user.
"Installer" user can change the "User" and "Advanced User" password.
.jpg)
Customise
Customise your SMART EVO according to the type of pumping system.
.jpg)
Display
Visualization of the status of inputs and outputs.
The status of the commands on the electronic board can be checked without opening the panel.
.jpg)
Alarms history
Visualization of the panel's alarm history (resettable)